Orifice Plate Flow Meter: How It Works and How to Calculate Flow
Table of Contents
- How does an orifice plate flow meter calculate flow?
- How does an orifice plate flow meter work?
- The parts of an orifice plate flow meter
- Where are the pressure taps placed?
- What is the beta ratio of an orifice plate flow meter?
- What is the discharge coefficient of an orifice plate?
- What is the orifice plate flow meter formula?
- Why is flow proportional to the square root of differential pressure?
- How do you calculate flow through an orifice plate? A solved example
- Solved example
- Orifice plate flow meter calculator
- How do you size an orifice plate flow meter?
- How much straight pipe does an orifice plate flow meter need?
- How accurate is an orifice plate flow meter?
- What problems are common with orifice plate flow meters?
- Pros and cons of an orifice plate flow meter
- Pros
- Cons
- Myth vs fact: orifice plate flow meter
- Industrial applications of the orifice plate flow meter
- Refinery
- Water and wastewater plant
- HVAC
- Chemical plant
- Frequently asked questions
- What is the working principle of an orifice plate flow meter?
- What is a good beta ratio for an orifice plate flow meter?
- Which side of the orifice plate faces upstream in the line?
- What is the typical discharge coefficient of a sharp edged orifice?
- How do you convert DP to flow for an orifice plate flow meter?
- Can an orifice plate flow meter measure gas and steam too?
An orifice plate flow meter is still the most common way to measure liquid, gas and steam flow in US plants, because it is just a drilled plate with a DP transmitter across it. The pressure drop across that plate gives you the flow, once you know the beta ratio, the discharge coefficient and the square root law.
Each of those gets its own section below, followed by a 4 inch (102.3 mm) orifice plate flow meter example for water, solved by hand. Engineering ToolBox puts the discharge coefficient of a sharp edged plate near 0.60, which is why the bore passes only about 60 percent of the ideal flow.
How does an orifice plate flow meter calculate flow?
An orifice plate flow meter calculates flow from the pressure drop across a thin plate with a sharp edged bore. Flow equals the discharge coefficient times the bore area times the square root of 2ΔP divided by density, corrected by 1 / √(1 − β⁴). Because flow follows the square root of DP, doubling the flow raises the DP four times.
How does an orifice plate flow meter work?
An orifice plate flow meter forces the fluid through a bore smaller than the pipe, which speeds it up and drops its pressure. A pair of taps and a DP transmitter measure that drop, and the drop tells you the flow.
Bernoulli’s equation is the whole idea: where velocity rises, static pressure falls. The jet keeps narrowing just past the plate, and that narrowest point, the vena contracta, is where pressure is lowest.
Downstream, the jet spreads out and pressure recovers, but not all the way. The part that never comes back is the permanent loss of the orifice plate flow meter, and you pay for it in pump energy.

The parts of an orifice plate flow meter
Every orifice plate flow meter has four pieces, and each one adds its own share of error.
- The plate is a flat stainless disc with a square edged bore. Emerson’s Rosemount 1495 data sheet lists a default thickness of 0.125 inches (3.2 mm) for 2 to 6 inch lines.
- Orifice flanges are drilled to hold the plate and set the tap location. Kleev supplies orifice plates and assemblies for these flange sets.
- Impulse lines carry pressure from the taps to an instrument valve manifold for isolating and equalizing.
- The DP transmitter, a flow transmitter, reads the differential and sends 4 to 20 mA, often with square root extraction built in.
Where are the pressure taps placed?
The Wikipedia article on the sharp edged orifice and its tap layouts describes three standard positions. Flange taps sit 1 inch (25.4 mm) from each face, corner taps sit at the plate, and D and D/2 taps sit one diameter upstream and half a diameter downstream.
Tap position changes both the measured DP and the coefficient. Always use the Cd that matches the taps on your orifice plate flow meter.
What is the beta ratio of an orifice plate flow meter?
The beta ratio is the bore diameter divided by the pipe inside diameter, β = d / D. It sets how hard the orifice plate flow meter squeezes the flow, and so how much DP and permanent loss you get.
A small beta gives a big DP and a big loss. A large beta is easier on the pump but gives a small DP that is hard to read at low flow.
An ABB data sheet quoting ISO 5167 gives a valid beta range of 0.2 to 0.75, a minimum bore of 0.49 inches (12.5 mm) and pipe IDs of 2 to 39 inches (50 to 1000 mm). Outside that window an orifice plate flow meter needs calibration instead of standard coefficients.
What is the discharge coefficient of an orifice plate?
The discharge coefficient, Cd, is real flow divided by ideal flow, and for a sharp edged orifice plate flow meter it sits near 0.6. It corrects Bernoulli for jet contraction and friction at the bore.
Engineering ToolBox publishes an orifice, nozzle and venturi coefficient table showing Cd of 0.608 at beta 0.5 and a Reynolds number of 100,000. The same table gives 0.62 at a Reynolds number of 10,000, so Cd drifts up as flow drops.
Wikipedia lists 0.60 to 0.63 for sharp edged plates with standard taps. Conical entrance plates run 0.73 to 0.734 and quarter circle plates 0.77 to 0.85, which suits viscous fluids.
What is the orifice plate flow meter formula?
The orifice plate flow meter formula combines Bernoulli, continuity and the discharge coefficient in one line. In SI units it gives flow in m3/s from bore area in m2, DP in Pa and density in kg/m3.
Q = Cd × A₀ × √(2ΔP / ρ) / √(1 − β⁴)
US field form: Q = 5.67 × Cd × d² × √(h / SG) / √(1 − β⁴)
Where: Q = flow, m3/s (or gpm); Cd = discharge coefficient; A₀ = πd² / 4; ΔP = differential, Pa; ρ = density, kg/m3; β = d / D; d = bore, inches; h = DP, inH2O; SG = specific gravity.
The term 1 / √(1 − β⁴) is the velocity of approach factor. At beta 0.5 it equals 1.0328, adding about 3.3 percent to the flow of the orifice plate flow meter.
We derived the 5.67 constant by converting inches, inH2O and gpm into the SI equation for water at 60 °F (15.6 °C). Both forms give the same answer to four figures.
Why is flow proportional to the square root of differential pressure?
Pressure drop grows with velocity squared, so flow grows with the square root of DP. Engineering ToolBox puts it plainly: ten times the flow needs a hundred times the pressure difference.
That fact limits the turndown of every orifice plate flow meter. Ranged 0 to 100 inH2O (0 to 24.9 kPa), half flow gives 25 inH2O and 10 percent flow gives just 1 inH2O.
Extract the square root in the transmitter or in the DCS, never in both. A double extraction makes the orifice plate flow meter read high across the range.
How do you calculate flow through an orifice plate? A solved example
Find beta, the velocity of approach factor and the bore area, then put the DP into the formula. The orifice plate flow meter example below uses water in a 4 inch Schedule 40 line.
Solved example
Given: water at 60 °F (15.6 °C), SG 1.0, pipe ID 4.026 inches (102.3 mm), bore 2.013 inches (51.1 mm), flange taps, Cd 0.61 and a DP of 100 inH2O (24.9 kPa).
- Beta: β = 2.013 / 4.026 = 0.500, so β⁴ = 0.0625.
- Velocity of approach factor: 1 / √(1 − 0.0625) = 1 / 0.9682 = 1.0328.
- Bore squared: d² = 2.013² = 4.052 square inches.
- Root term: √(100 / 1.0) = 10.
- Flow: Q = 5.67 × 0.61 × 4.052 × 10 × 1.0328 = 144.7 gpm (32.9 m3/h).
- Reynolds check: Re = 3160 × 144.7 / 4.026 = about 113,600 for 1 cP water, above the 10,000 floor for this beta.
At 25 inH2O (6.2 kPa) the same orifice plate flow meter passes 72.4 gpm (16.4 m3/h), exactly half.
Pipe velocity at 144.7 gpm is about 3.65 ft/s (1.11 m/s), normal for water. The Reynolds formula in the last step is covered in our Reynolds number guide.
Orifice plate flow meter calculator
Check your own orifice plate flow meter numbers in SI units below. For the example, enter a pipe ID of 102.3 mm, a bore of 51.1 mm, Cd 0.61, 24.9 kPa and 999 kg/m3, and you should get about 32.8 m3/h, the hand result within rounding.
How do you size an orifice plate flow meter?
Choose the DP you want at maximum flow, then solve the formula backwards for the bore. Then check that beta, Reynolds number and straight run stay inside the limits.
- Collect maximum, normal and minimum flow, plus SG and viscosity at the coldest case.
- Pick a DP at maximum flow, such as 100 inH2O (24.9 kPa).
- Solve for the bore with Cd near 0.61, then recheck Cd for the new beta.
- Confirm beta is 0.2 to 0.75 and Reynolds number at minimum flow stays above the floor.
- Compare the straight run you have with the run the beta needs.
Keep normal flow high in the range. An orifice plate flow meter running at 30 percent of maximum flow sits at only 9 percent of its DP span.
How much straight pipe does an orifice plate flow meter need?
The ABB data sheet based on ISO 5167 lists 14 diameters after a single 90° bend at beta 0.5, or 7 diameters if you accept 0.5 percent extra uncertainty. Wikipedia gives 20 to 40 diameters upstream, depending on Reynolds number, unless you fit a flow conditioner.
Larger betas need longer runs. If the piping cannot give you the run, an orifice plate flow meter is the wrong choice for that spot.

How accurate is an orifice plate flow meter?
Engineering ToolBox lists orifice accuracy at 2 to 4 percent of full scale with about 4:1 rangeability. A clean, sharp, well installed orifice plate flow meter can do better.
The big losses come from a rounded edge, a backward plate, short straight run and plugged impulse lines. None of these raise an alarm, so the orifice plate flow meter just reads wrong.
What problems are common with orifice plate flow meters?
Most orifice faults are installation or maintenance problems, not transmitter faults. Our flow meter troubleshooting guide covers other meter types; this table is for orifice runs.
| Symptom | Likely cause | Fix |
|---|---|---|
| Orifice plate flow meter reads low over time | Bore edge worn round by erosion | Pull the plate and replace it if the edge reflects light |
| Orifice plate flow meter off from day one | Plate installed backward | Face the sharp edge and stamped side upstream |
| Reads high across the range | Square root applied twice | Turn off one of the two extractions |
| Noisy signal at low flow | DP near the bottom of range | Rerange, add damping or fit a smaller bore |
| Zero shift on a liquid line | Gas trapped in impulse lines | Slope lines down to the taps and vent |
| Zero shift on a gas line | Liquid in impulse lines | Mount the transmitter above the taps |
To zero the transmitter, follow our 3 valve manifold procedure. Opening the wrong valve first can put full line pressure on one side of the cell.
A loop check splits a wiring fault from a process fault. This guide to the 4 to 20 mA current loop shows how to measure loop current and compare it with the expected DP.
Pros and cons of an orifice plate flow meter
An orifice plate flow meter is cheap, simple and well standardized, but it wastes pressure and has narrow turndown. Weigh both lists against your service.
Pros
- Low cost orifice plate flow meter, even in large lines
- No moving parts
- Works on liquid, gas and steam
- ISO 5167 coefficients, so no wet calibration inside the limits
- Quick plate swaps when the range changes
Cons
- High permanent loss compared with a venturi
- About 4:1 rangeability with one transmitter
- Long straight runs
- Accuracy drops as the edge wears
- Impulse lines can plug, freeze or trap gas
Engineering ToolBox gives the permanent head loss of an orifice plate flow meter at roughly 70 to 75 percent of the differential for an area ratio of 0.5. On a big cooling water line, that loss shows up on the pump bill.
Myth vs fact: orifice plate flow meter
A few common beliefs lead straight to bad orifice plate flow meter readings. These are the ones we see most in the field.
The orifice plate flow meter pressure drop is all lost energy.
Part of the drop recovers downstream; the permanent loss is only a share of the measured DP.
A Cd of 0.6 works for every orifice plate flow meter.
Cd changes with beta, taps and Reynolds number, from 0.594 to 0.64 in the Engineering ToolBox table.
Flow and DP rise in a straight line.
Flow follows the square root of DP, so half flow gives a quarter of the DP.
An orifice plate flow meter never needs inspection.
Erosion rounds the edge and deposits shrink the bore, and both shift the reading silently.

Industrial applications of the orifice plate flow meter
An orifice plate flow meter shows up wherever a plant needs a low cost reading on clean liquid, gas or steam. We see it every week in these four places.
Refinery
Fuel gas to heaters and steam to strippers often run through an orifice plate flow meter with flange taps. Plates are swapped at turnaround when rates change.
Water and wastewater plant
Plants use orifice runs on clean water, chemical feed and aeration air. Raw sewage with solids suits a magnetic meter from our flowmeter range.
HVAC
Fixed orifices with test ports balance chilled and hot water coils. A technician reads the DP with a differential pressure gauge and sets the balancing valve.
Chemical plant
Reactor feeds and nitrogen headers use an orifice plate flow meter with alloy plates such as C-276. Remote seals keep aggressive fluids out of the transmitter.
Add a pressure transmitter and a temperature input so the DCS can compensate gas density. Without that, a gas orifice plate flow meter drifts whenever line pressure moves.
Frequently asked questions
What is the working principle of an orifice plate flow meter?
An orifice plate flow meter works on Bernoulli’s principle. The plate narrows the flow, velocity rises through the bore and static pressure falls. A DP transmitter reads the difference between the upstream and downstream taps, and flow is found from the square root of that difference times a constant.
What is a good beta ratio for an orifice plate flow meter?
ISO 5167, as quoted in an ABB data sheet, allows beta from 0.2 to 0.75 for standard coefficients. Many engineers aim near the middle so the DP is easy to read and the straight run stays short. A beta of 0.5 is a common, comfortable choice for water.
Which side of the orifice plate faces upstream in the line?
The sharp, square edge of the bore faces upstream, and the bevel, if there is one, faces downstream. Most plates carry the stamped data on the upstream side. A plate fitted backward behaves like a different shape, so the coefficient changes and the orifice plate flow meter reads wrong.
What is the typical discharge coefficient of a sharp edged orifice?
Wikipedia gives 0.60 to 0.63 for sharp edged plates with corner, flange or D and D/2 taps. Engineering ToolBox shows 0.608 at a beta of 0.5 and a Reynolds number of 100,000. Use the exact value from the standard equation for your plate when accuracy matters.
How do you convert DP to flow for an orifice plate flow meter?
Take the square root of the measured DP divided by the full scale DP, then multiply by the full scale flow. With 100 inH2O equal to 144.7 gpm, a reading of 25 inH2O gives the square root of 0.25, which is 0.5, so the flow is 72.4 gpm.
Can an orifice plate flow meter measure gas and steam too?
Yes, plates are widely used on natural gas, fuel gas and steam. For compressible flow you add an expansibility factor and compensate density for pressure and temperature. Wikipedia notes that small beta restriction plates in gas service must be checked for choking, which a standard thin plate avoids.
