Differential Pressure Transmitter: How It Works, Hookup and 4 to 20 mA Scaling

Differential pressure transmitter working, hookup and scaling featured image

Differential Pressure Transmitter: How It Works, Hookup and 4 to 20 mA Scaling

WRITTEN BYKleev Technical Staff
PUBLISHED 
LAST UPDATED 
READ TIME12 min
VIEWS

A differential pressure transmitter measures the difference between two process pressures and sends it to the control system as a 4 to 20 mA signal. If you need to understand the cell, pipe the impulse lines right the first time and check the output scaling without guessing, start with the high and low sides.

After that come the sensing cell, hookups, zero and span, and a calculator that converts measured dP to mA and back.

How does a differential pressure transmitter work?

A differential pressure transmitter has a high side and a low side, each sealed by an isolating diaphragm that passes pressure through fill oil to one sensing cell. The cell, capacitive or piezoresistive, responds only to the difference, and the electronics scale that dP from the lower range value to the upper range value as 4 to 20 mA.

What is a differential pressure transmitter?

A differential pressure transmitter is a field instrument with two process connections that reports the difference between them, not either pressure alone. Many plants simply call the differential pressure transmitter a DP cell.

The Wikipedia entry on the pressure sensor family points out that a gauge sensor is really a differential sensor with one side open to atmosphere. A differential pressure transmitter pipes both sides to the process, so it can read across a filter, an orifice plate or a liquid column.

For a local reading only, a differential pressure gauge may be enough. When the value must reach a DCS or PLC, you need a differential pressure transmitter.

What are the high and low sides of a differential pressure transmitter?

The high side (H) connects to the point you expect to carry the higher pressure, and the low side (L) connects to the other point. The differential pressure transmitter reports dP = H minus L, so a swapped pair reads negative.

On a flow element, the differential pressure transmitter H port goes to the upstream tap. On a filter, H goes to the dirty inlet, so a loading filter drives the signal up.

For a tank, H normally goes to the bottom tap and L to the vapor space or atmosphere. Wet and dry leg math is in our post on hydrostatic level measurement.

Differential pressure transmitter working principle: inside the cell

Inside the differential pressure transmitter, two isolating diaphragms pass process pressure through sealed fill oil to a single sensing element. The element bends in proportion to the difference, and the electronics turn that movement into a digital value and then a current.

Emerson’s Engineer’s Guide to DP Flow Measurement describes the capacitive design: a flexible center diaphragm sits between two plates, with oil filled chambers on both sides. When H pressure rises above L, the diaphragm moves toward the low side plate, one capacitance rises and the other falls, and the ratio gives dP.

The same guide notes that the isolating diaphragms are usually 316 stainless steel and the standard fill fluids are light silicone oils. ABB adds that Inconel diaphragms are used where salt water would attack stainless.

Capacitive vs piezoresistive cells

A piezoresistive cell uses strain gauges formed on silicon, wired as a Wheatstone bridge, whose resistance changes as the element flexes. Wikipedia calls piezoresistive strain gauge sensing the most common technology for general purpose pressure measurement.

Both cell types do the same job in a differential pressure transmitter. You pick the range, static rating and wetted materials, and the cell comes with the model.

Differential pressure transmitter hookup diagram for gas, liquid and steam service
Differential pressure transmitter hookup: above the taps for gas, below for liquid and steam, with water filled legs for steam above 250 °F (121 °C).

What is a differential pressure transmitter used for?

A differential pressure transmitter is used for three main jobs: filter and strainer dP, flow across a primary element, and liquid level or density. ABB lists filtration, gas flow, condenser level and reaction monitoring among differential pressure transmitter uses.

  • Filter dP: the cell reads the loss across a filter or strainer, and the trend tells you when to change elements.
  • Flow: with an orifice plate, venturi or pitot, the differential pressure transmitter sees dP rise with the square of flow. You can check the square root math with this DP flow square root calculator, and Kleev also supplies dedicated flow transmitters.
  • Level: liquid head above the bottom tap gives dP, the basis of many level transmitters on closed vessels.

For plain gauge or absolute readings, a single port pressure transmitter is the simpler choice.

How do you install a differential pressure transmitter on gas, liquid and steam?

Install the differential pressure transmitter so the impulse lines drain or vent back to the process: above the taps for gas, below for liquid and steam. These rules come from the Emerson Rosemount 3051 reference manual.

Gas service

Put the taps in the top or side of the line and mount the differential pressure transmitter beside or above them, so any condensed liquid drains back into the pipe. Emerson asks for a slope of at least 1 inch per foot (8 cm/m) downward from the transmitter toward the process.

Liquid service

Put the taps on the side of the line so sediment does not settle on the isolators, and mount the differential pressure transmitter beside or below them. Slope the lines at least 1 inch per foot (8 cm/m) upward from the transmitter, and point the drain and vent valves upward, so gas bubbles vent back into the line.

Steam service

Use side taps and mount the differential pressure transmitter below them so the lines stay full of condensate. Emerson says to fill the lines with water above 250 °F (121 °C) so live steam never reaches the differential pressure transmitter.

The Emerson DP flow guide adds that both condensate legs must sit at the same height, or unequal water head shows up as false dP.

Always fit a manifold between the taps and the differential pressure transmitter so you can isolate, equalize and vent. Our 3 valve manifold operation guide gives the sequence, and Kleev instrument manifolds come in 3 and 5 valve styles.

How do you zero a differential pressure transmitter?

To zero a differential pressure transmitter, isolate it from the process, open the equalizer so H and L see the same pressure, and trim the output to 4.00 mA. Do it at operating static pressure, because a bench zero may not hold at line pressure.

Zero (the lower range value, LRV) sets which dP gives 4 mA. Span is the distance from LRV to the upper range value (URV), which gives 20 mA.

A zero trim corrects the sensor reading; reranging changes LRV and URV without applying pressure. Mixing them up is why a differential pressure transmitter reads right on the bench and wrong in the plant.

For a span check on a differential pressure transmitter, apply a known pressure to H with L vented. Check at 0, 25, 50, 75 and 100 percent and record the as found and as left values.

Differential pressure transmitter 4 to 20 mA output scaling

A differential pressure transmitter output is linear in dP: 4 mA at LRV, 20 mA at URV, and 16 mA of signal in between. Wikipedia’s current loop article explains why the zero is 4 mA and not 0: the live zero keeps a loop powered device running, so 0 mA means a fault.

% span = (dP − LRV) / (URV − LRV) × 100

mA = 4 + 16 × (dP − LRV) / (URV − LRV)

dP = LRV + (mA − 4) / 16 × (URV − LRV)

Where: dP, LRV and URV in the same unit, inH2O (kPa); 1 inH2O = 0.2491 kPa

The same article says currents below 3.8 mA or above 20.5 mA are taken as a fault. For loop wiring and power, see this primer on the 4 to 20 mA current loop.

A differential pressure transmitter on flow may be set to square root output. The Emerson DP flow guide warns that taking the square root in both the transmitter and the control system gives large errors, so do it in one place only.

DP transmitter 4 to 20 mA scaling card with worked example
Differential pressure transmitter scaling card: 75 inH2O (18.7 kPa) on a 0 to 200 inH2O range gives 37.5% and 10.00 mA.

How do you calculate the mA output of a differential pressure transmitter? A solved example

Take the measured dP minus LRV, divide by the span, multiply by 16 and add 4. The worked example uses a filter differential pressure transmitter.

Solved example

A differential pressure transmitter is calibrated 0 to 200 inH2O (0 to 49.8 kPa). The process reads a dP of 75 inH2O (18.7 kPa).

  1. Span = URV minus LRV = 200 minus 0 = 200 inH2O (49.8 kPa).
  2. Percent of span = 75 / 200 = 0.375, or 37.5%.
  3. Output = 4 + 16 × 0.375 = 4 + 6.00 = 10.00 mA.
  4. Reverse check: a reading of 14.2 mA gives (14.2 minus 4) / 16 = 63.75%, so dP = 0.6375 × 200 = 127.5 inH2O (31.8 kPa).
  5. If the same dP fed a flow loop, flow would be √0.375 = 61.2% of full scale, not 37.5%.

The calculator below runs the same differential pressure transmitter math in both directions.

DP transmitter scaling calculator

Result appears here

Why does my differential pressure transmitter read wrong?

Most wrong readings come from the impulse lines, not the electronics: trapped gas, trapped liquid, plugging or unequal legs. Check the zero with the manifold first, then work through the table.

SymptomLikely causeFix
Output below 4 mA when flow or filter loading risesH and L lines swappedSwap the lines at the manifold, or confirm the H mark on the flange
Liquid reading drifts or jumpsGas bubble trapped in one legVent both sides; check the lines slope up to the pipe
Gas reading offset or erraticCondensate sitting in a legDrain the legs; mount the transmitter above the taps
Steam flow offset after startupCondensate legs at different heights or not yet fullFill both legs, level them, zero at thermal equilibrium
Output pinned at 20.5 mA or abovedP above URV, or a blocked low side tapCheck the range, then blow down the L tap
Flow noisy near zeroSquare root amplifies small dP noiseUse a low flow cutoff and take square root in one place only
Flowchart for checking DP transmitter zero and wrong readings
Zero and reading check: equalize, confirm 4.00 mA at zero dP, then look at the impulse legs and range settings.

Where the process plugs or freezes taps, a differential pressure transmitter with remote diaphragm seals removes the impulse lines.

Pros and cons of a differential pressure transmitter

A differential pressure transmitter is one well known instrument that can measure flow, level and filter loading. Its weak point is the impulse piping, which needs care in design and upkeep.

Pros

  • One instrument type covers flow, level, density and filter dP
  • Standard 4 to 20 mA output, often with HART
  • Rerange and zero trim without changing hardware
  • Works on gas, liquid and steam with the right hookup

Cons

  • Impulse lines can plug, freeze, leak or trap fluid
  • Flow turndown is limited by the square law
  • Zero can shift with static line pressure
  • Steam and hot service need water filled legs or seals

Myth vs fact: differential pressure transmitter setup

A few habits cause most differential pressure transmitter errors we see in the field.

MYTH

0 mA from a differential pressure transmitter means zero dP.

FACT

Zero dP at LRV is 4 mA. Wikipedia notes that below 3.8 mA is treated as a fault, so a dead loop is not a zero reading.

MYTH

Taking the square root in the transmitter and again in the DCS is a safe double check.

FACT

Emerson’s DP flow guide warns that doing it in both places causes large errors. Pick one place and document it.

MYTH

A bench zero is good enough for service.

FACT

Leg head and static pressure move the zero. Emerson recommends zeroing in place after the system reaches thermal equilibrium.

MYTH

Mounting position does not matter if the lines are tight.

FACT

Gas needs the transmitter above the taps and liquid and steam need it below. Wrong placement traps fluid and shifts the reading.

Industrial applications of the differential pressure transmitter

The differential pressure transmitter shows up in almost every process unit, in plant uses like these.

Refinery

A differential pressure transmitter on an orifice run measures fuel gas and crude flow. ABB also lists condenser and crude distillation level among common DP duties.

Water and wastewater plant

Each media filter gets a differential pressure transmitter across inlet and outlet. Operators start a backwash when the dP trend reaches its set point.

HVAC

Low range units in inH2O read the drop across air filters and coils. Wikipedia notes inch of water is the usual unit for small differentials across an HVAC coil.

Chemical plant

A differential pressure transmitter watches level in reaction vessels, including low temperature reaction tanks named by ABB. Seals keep corrosive media off the cell.

Frequently asked questions

How does a differential pressure transmitter measure flow in a pipe?

A differential pressure transmitter reads the dP across an orifice plate, venturi or pitot. Flow rises with the square root of that dP, so the transmitter or the control system takes the square root. Emerson warns against doing it in both places, because the doubled math gives large errors.

What is the difference between a pressure transmitter and a DP transmitter?

A gauge or absolute transmitter has one process port and reads against atmosphere or vacuum. A differential pressure transmitter has two ports, high and low, and reports only the difference between them. That lets it measure flow, level and filter loading while ignoring the static line pressure common to both sides.

Which side of a DP transmitter goes upstream on a filter?

Connect the differential pressure transmitter high side to the upstream, dirty side of the filter and the low side to the clean outlet. As the filter loads, upstream pressure rises relative to downstream and the signal climbs toward 20 mA. If you swap them, the reading goes below 4 mA.

How do you calculate percent of span from a 4 to 20 mA signal?

Subtract 4 from the measured current and divide by 16. For example, 14.2 mA gives (14.2 minus 4) / 16 = 63.75% of span. On a 0 to 200 inH2O range that equals 127.5 inH2O, or about 31.8 kPa, which the calculator above confirms in both directions.

Why must steam impulse lines be filled with water before startup?

Filled legs keep live steam off the sensing diaphragm and give equal, stable head on both sides. Emerson says to fill the lines with water above 250 °F (121 °C) and to keep both condensate legs at the same height, then zero after the system reaches thermal equilibrium.

Can one differential pressure transmitter measure both level and flow?

Not at the same time from one pair of taps, because level and flow need different tap points and range settings. You can configure the same model for either job, though. ABB’s multisensor models also report absolute pressure alongside dP, but each still reads only one differential.